Toshiba TOSVERT VF-FS1 Instruction Manual page 98

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

     An example of the connection of the relay output terminals
• Output terminal setting
6
6.1.2
• Function
[Parameter setting]
[Parameter setting]
Note: Select the
Output of the low-speed signal (ON signal) between the RY and RC terminals is the factory default
setting of the output terminal selection parameter. This setting must be changed to invert the polarity of
the signal.
[Parameter setting]
Title
Output terminal selection 1A (RY-RC)
Output of designated frequency reach signal
: Speed reach detection band
When the output frequency becomes equal to the setting by designated frequency ±
OFF signal is generated.
Title
Function
Speed reach detection band
Title
Function
Output terminal
selection 1A
(RY-RC)
parameter to specify FLA-FLC-FLB terminal output.
Function
0-255
(⇒ See page K-17)
0.0 ∼
Adjustment range
0-255
6: RCH (designated frequency - ON signal), or
7: RCHN (designated frequency - OFF signal)
(⇒ See page K-17)
F-2
Adjustment range
Setting value
4 (ON signal)
5 (OFF signal)
Adjustment range
(Hz)
Setting value
E6581381
or
, an ON or
Default setting
2.5

Advertisement

Table of Contents
loading

Table of Contents