4. Parameters

4.1. Communication parameters

This option doesn't operate if these parameters are not correctly set.
4.1.1.
Relation parameters for VF-S15/MB1
Communi
Title
cation No.
0003
Command mode selection
cmod
Frequency setting mode
0004
fmod
selection 1
Setting of acceleration /
0519
f519
deceleration time unit
Integrating wattmeter display
0749
f749
unit selection
Number of motor pole pair for
0856
f856
communication
0898
Reset mode selection (*3)
f898
0899
Communication function reset
f899
(*1): 0.1s unit is selected as default setting.
(*2): Default setting values vary depending on the capacity.
(*3): When you reset by f899=1 setting, or trip is requires a reboot of inverter, the inverter is rebooted
regardless of the parameter setting.
Function
0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
3: CANopen communication
4: Communication option
0: Setting dial 1 (save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sr0
0: -
1: 0.01s unit (after execution: 0)
2: 0.1s unit (after execution: 0)
0: 1.0=1kWh
1: 1.0=10kWh
2: 1.0=100kWh
3: 1.0=1000kWh
4: 1.0=10000kWh
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
0: Clear trip without disrupting communication by
reset command from communication option.
Reset and restart by reset command from panel
keypad, terminal block or RS485 communication.
1: Reset
2: Clear trip
3 to 5: -
0: -
1: Reset (after execution: 0)
- 19 -
Description
E6582051
Default
setting
1
0
0
(*1)
(*2)
2
0
-