Dc Braking - Toshiba TOSVERT VF-FS1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

6.7

DC braking

6.7.1
DC braking
: DC braking starting frequency
: DC braking current
: DC braking time
• Function
A large braking torque can be obtained by applying a direct current to the motor. These parameters
set the direct current to be applied to the motor, the application time and the starting frequency.
[Parameter setting]
Title
DC braking starting frequency
DC braking current
DC braking time
Note1: During DC braking, the overload protection sensitivity of the inverter increases. The DC braking
current may be adjusted automatically to prevent tripping.
Note 2: During DC braking, the carrier frequency is 6kHz irrespective of the setting of parameter
(PWM carrier frequency).
Function
Output frequency [Hz]
Set frequency
DC braking starting frequency
0
Output current [A]
0
Operation signal (F or R)
F-23
Adjustment range
0.0-
(Hz)
0-100 (%) / (A)
0.0- 20.0 (sec)
DC braking
Time [s]
DC braking current
DC braking time
ON
OFF
E6581381
Default setting
0.0
6
50
1.0