Communication Parameters - Toshiba TOSVERT VF-AS3 Instruction Manual

Embedded ethernet function
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Comm.
Title
No.
F899
0899
Communication function reset
(*1): 0.1s unit is selected as default setting.
(*2): Default setting values vary depending on the capacity.

2.2. Communication parameters

Comm.
Title
No.
C081 to
C081 to
Device Name 1-16 (*1)
C096
C096
C606
C606
Emb Eth. Communication
C607
C607
error operation
Emb Eth. Preset speed at
C608
C608
communication error
Emb Eth. Communication
C609
C609
error detection
Emb Eth. IP setting mode
C610
C610
(*1)
C611 to
C611 to
Emb Eth. IP address setting
C614
C614
value (*1)
C615 to
C615 to
Emb Eth. Subnet mask
C618
C618
setting value (*1)
C619 to
C619 to
Emb Eth. Default gateway
C622
C622
setting value (*1)
C641 to
C641 to
C650
C650
Parameter name
Parameter name
Emb Eth. Communication
error detection delay
Emb Eth. Scanner input
select 1 to 10
Description
0: -
1: Reset option and inverter (after execution: 0)
Description
Max 16 characters
Default setting1 function ([tyP] = "3") does not
work for this parameter.
0.0 - 100.0 sec.
0: Turn off bit 10, 14 and 15 of FA36
1: Continue running
2: Deceleration stop
3: Coast stop
4: Network error stop (E-43 trip)
5: Preset speed operation (by C608 setting)
0: None
1 to 15: Preset speed
0: Always
1: Communication command (Frequency
command and command from Emb Eth.)
enabled
2: 1 + during run
0: Fixed
1: BOOTP
2: DHCP
The IP address of the device.
These fields are effective settings at [C610] = "0".
The subnet mask of the device.
These fields are effective settings at [C610] = "0".
The gateway IP address of the device.
These fields are effective settings at [C610] = "0".
0: No action
1: FA36 (Emb Ethernet command 1)
2: FA38 (Emb Ethernet command 2)
3: FA37 (Emb Ethernet frequency command)
4: FA40 (Emb Ethernet torque command)
5: FA50 (Terminal output data)
6: FA51 (Terminal FM data)
7: FA52 (Terminal AM data)
8: F601 (Stall prevention level 1)
9: F441 (Power running torque limit level 1)
10: F443 (Regenerative torque limit level 1)
11: F460 (Speed control response 1)
12: F461 (Speed control stabilization coefficient 1)
13: ACC (Acceleration time 1) (*2)
14: dEC (Deceleration time 1) (*2)
15: UL (Upper limit frequency)
16: vb (Manual torque boost 1)
17: vLv (Base frequency voltage 1)
8
E6582125
Default
setting
-
Default
setting
0
0.0
4
0
1
2
0.0.0.0
0.0.0.0
0.0.0.0
C641: 1
C642: 3
C643 to
C644: 0