Display Of Trip Information - Toshiba TOSVERT VF-FS1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

8.2

Display of trip information

8.2.1
Trip code display
If the inverter trips, an error code is displayed to suggest the cause. Since trip records are retained, information
on each trip can be displayed anytime in the status monitor mode.
Display of trip information
Error code
(*)
(Continued overleaf)
Failure
code
0000
No error
0001
Overcurrent during acceleration
0002
Overcurrent during deceleration
0003
Overcurrent during constant speed operation
0004
Load-side overcurrent during start-up
0005
Armature-side overcurrent during start-up
0008
Input phase failure or exhaustion of main circuit capacitor
0009
Output phase failure
000A
Overvoltage during acceleration
000B
Overvoltage during deceleration
000C
Overvoltage during constant-speed operation
000D
Inverter overload trip
000E
Motor overload trip
0010
Overheating trip or thermal detector failure
0011
Emergency stop
2
0012
E
PROM fault 1 (writing error)
2
E
PROM fault 2 (initialization error) or power-off during the setting of
0013
2
0014
E
PROM fault 3 (reading error)
0015
Inverter RAM fault
0016
Inverter ROM fault
0017
CPU fault trip 1
0018
Communication error
001A
Current defector fault
001B
Network error
001D
Small-current trip
001E
Undervoltage trip
0020
Over-torque trip
0022
Ground fault
0025
Overcurrent flowing in element during acceleration
H-5
Description
E6581381
8

Advertisement

Table of Contents
loading