Remote mode selection,
Ex.2
Operation frequency setting, running and stopping using external
signals.
(1)
Wiring
MCCB
R/L1
S/L2
T/L3
(2)
Parameter setting
Title
Command mode selection
Frequency setting mode selection 1
(3)
Operation
Run/stop: ON/OFF input to F-CC, R-CC. (Set SW4 to Sink logic)
Frequency setting: VIA and VIB: 0-10Vdc (External potentiometer)
VIA: Input 4-20mAdc.
Use the VIA (SW3) slide switch to switch between voltage and current to the VIA terminal.
Voltage input: V side
Current input: I side
Please turn off the lamp by pressing the
PA/+
PC/-
*
Noise
Power circuit
filter
Control
circuit
CC
VIA
VIB
PP
(Otherwise, input voltage signal (0~10V) between the terminals VIA-CC.)
Function
LOC
key when the LOC/REM key lamp is lit.
REM
C-7
Motor
U/T1
V/T2
IM
W/T3
Run forward signal
F
R
Run backward signal
Common
CC
Voltage signal: 0∼10V, Current signal: 4∼20mA
External potentiometer
Setting value
0
1or2
E6581381
3