Toshiba TOSVERT VF-FS1 Instruction Manual page 210

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

Communication
Title
No.
0005
0006
0007
0008
11
0009
0010
0011
0012
0013
0014
0409
Minimum
setting unit
Function
Unit
Panel/Commun
ication
Meter selection
-
Meter adjustment
-
Default setting
-
Forward/reverse
-
run selection
(Operation panel
operation)
Acceleration time
S
0.1/0.1
1
Deceleration time
S
0.1/0.1
1
Maximum
Hz
0.1/0.01
frequency
Upper limit
Hz
0.1/0.01
frequency
Lower limit
Hz
0.1/0.01
frequency
Base frequency 1
Hz
0.1/0.01
Base frequency
V
1/0.1
voltage 1
Adjustment range
-
0: Output frequency
1: Output current
2: Set frequency
3: DC voltage
4: Output voltage command value
5: Input power
6: Output power
7: Torque
8: Torque current
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: - (do not select)
12: Frequency setting value (after
PID)
13: VIA Input value
14: VIB Input value
15: Fixed output 1 (Output current:
100%)
16: Fixed output 2 (Output current:
50%)
17: Fixed output 3 (Supposition
output at
=17)
18: Serial communication data
19: For adjustments (
displayed.)
-
-
-
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8. Call user-defined parameters
9. Cumulative fan operation time
record clear
-
0: Forward run
1: Reverse run
2: Forward run (F/R switching
possible)
3: Reverse run (F/R switching
possible)
0.0-3200
0.0-3200
30.0-200.0
0.5-
0.0-
25.0-200.0
50-330 (200V class)
50-660 (400V class)
K-2
E6581381
Default
User
setting
setting
0
set value is
-
0
0
*2
*2
80.0
50.0 (WP)
60.0 (WN)
0.0
50.0 (WP)
60.0 (WN)
*1
Reference
5.4
4.2.7
4.2.8
5.5
5.6
5.1.2
5.7
5.8
5.9
5.9
6.12.5

Advertisement

Table of Contents
loading

Table of Contents