• Communication parameters
Communication
Title
Function
No.
0800
Communication
rate
Parity
0801
Inverter number
0802
0803
Communication
error trip time
Communication
0805
waiting time
0806
Setting of master
and slave for
communication
between inverters
0811
Communication
command point 1
setting
0812
Communication
command point 1
frequency
0813
Communication
command point 2
setting
0814
Communication
command point 2
frequency
0829
Selection of
communication
protocol
0870
Block write data 1
0871
Block write data 2
0875
Block read data 1
0876
Block read data 2
0877
Block read data 3
0878
Block read data 4
0879
Block read data 5
0880
Free notes
Minimum
setting unit
Unit
Adjustment range
Panel/Commun
ication
-
-
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
-
-
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
-
1/1
0-255
s
1/1
0: (disabled)
1-100
s
0.01/0.01
0.00-2.00
-
-
0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in case
the master inverter fails)
2: Slave (Emergency stop tripping in
case the master inverter fails)
3: Master (transmission of frequency
commands)
4: Master (transmission of output
frequency signals)
%
1/1
0-100
Hz
0.1/0.01
0.0-500.0
%
1/1
0-100
Hz
0.1/0.01
0.0-500.0
-
-
0: Toshiba inverter protocol
1: Modbus RTU protocol
-
-
0: No selection
1: Command information 1
2: Command information 2
3: Frequency command
-
-
4: Output data on the terminal board
5: Analog output for communications
-
-
0: No selection
1: Status information
2: Output frequency
-
-
3: Output current
4: Output voltage
-
-
5: Alarm information
6: PID feedback value
-
-
7: Input terminal board monitor
8: Output terminal board monitor
-
-
9: VIA terminal board monitor
10: VIB terminal board monitor
-
1/1
0-65535
67
E6581160
Default
User
Reference
setting
setting
E6581158
3
6.22
1
0
0
0.00
0
0
6.5.2
6.22.1
0.0
100
50.0 (WP)
60.0
(WN, AN)
0
6.22
0
0
0
0
0
0
0
0
7