Parameters; Communication Parameters - Toshiba TOSVERT VF-AS1 Series Function Manual

Ethernet/ip option unit
Hide thumbs Also See for TOSVERT VF-AS1 Series:
Table of Contents

Advertisement

3. Parameters

3.1. Communication parameters

Set up the inverter parameters as follows. It is necessary to reset the inverter to update the parameter.
This option doesn't operate if these parameters are not correctly set.
Communi
Title
cation No.
0003
cmod
Command mode selection
Frequency setting mode
0004
fmod
selection 1
f576
0576
IP mode (*1)
0577-
f577-
IP address (*1)
0580
f580
0581-
f581-
IP Mask (*1)
0584
f584
0585-
f585-
IP Gate (*1)
0588
f588
0784-
f784-
MAC address
0789
f789
0792-
f792-
DEVICE NAME (*1)
0799
f799
0821
f821
Rate Setting (*1)
Function
0: Terminal input enabled
1: Operation panel input enabled
(including LED/LCD option input)
2: 2-wire RS485 communication input
3: 4-wire RS485 communication input
4: Communication option input
1: VI/II (voltage/current input)
2: RR/S4 (potentiometer/voltage input)
3: RX (voltage input)
4: Operation panel input enabled
(including LED/LCD option input)
5: 2-wire RS485 communication input
6: 4-wire RS485 communication input
7: Communication option input
8: Optional AI1 (differential current input)
9: Optional AI2 (voltage/current input)
10: UP/DOWN frequency
11: Optional RP pulse input
12: Optional high-speed pulse input
13: Optional binary/BCD input *
*Unsupported option
Use this parameter to select the IP address assignment
method.
0:Manual
1:BOOTP
2:DHCP
Refer to "3.2.2 Assigning IP addresses" for the details.
IP address of the card
These fields are editable when IP mode = 0.
Refer to "3.2.2 Assigning IP addresses" for the details.
Subnet mask of the card
These fields are editable when IP mode = 0.
Refer to "3.2.2 Assigning IP addresses" for the details.
Gateway IP address of the card
These fields are editable when IP mode = 0.
Refer to "3.2.2 Assigning IP addresses" for the details.
MAC address display
[XX-XX-XX-XX-XX-XX]
16 chars (These are 2 chars about one parameter.)
The device name is required if the card uses DHCP to
obtain its IP Address.
Refer to "3.2.1 DEVICE NAME" for the details.
This field is used to set the transmission speed and the
transmission mode of the card.
0:Autodetect(default)
1:10Mbps Full
2:10Mbps Half
3:100Mbps Full
4:100Mbps Half
- 7 -
Description
E6581581
Default
setting
0
1
0
0,0,0,0
0,0,0,0
0,0,0,0
-
-
(*2)
0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tosvert vf-ps1 seriesTosvert ipe001z