6.22 Parameters for options

: Parameter for option 1
: Parameter for option 2
: Parameter for option 3
: Parameter for option 4
: Parameter for option 5
These parameters can be used only when specific optional parts are installed. Do not use these parameters
unless such parts are installed.

6.23 Permanent magnetic motors

: Step-out detection current level
: Step-out detection time
: High-speed torque adjustment coefficient
• Function
If the permanent magnet motor (PM motor) steps out and if the exciting current increases (it increases
in such a case) and remains above the value set with
the inverter will judge the motor to be stepping out and trip it. At that time, the trip message
"
" is displayed.
Title
Step-out detection current level
Step-out detection time
High-speed torque adjustment coefficient
Note 1: When using an PM motor, consult your Toshiba dealer, since the inverter is not compatible with all
types of PM motors.
Note 2: The inverter may fail to detect step-out in some cases, because it uses an electrical method to detect
step-out. To avoid detection failures, you are recommended to install a mechanical step-out detector.
Note 3: There is no need adjust
otherwise instructed by Toshiba technical staff.)
Function
10 ~ 150 (%) / (A)
0.0: No detection
0.1 ~ 25.0 [s]
0.00 ~ 650.0
under normal conditions. (Do not change the setting, unless
F-83
: Parameter for option 6
: Parameter for option 7
: Parameter for option 8
: Parameter for option 9
: Parameter for option 10
for the period of time set with
Adjustment range
E6581381
6
,
Default setting
100
0.0
0.00