Toshiba TOSVERT VF-FS1 Instruction Manual page 237

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

(Continued)
Error code
Failure code
002E
0011
0012
0013
0014
0015
0016
0017
*
0018
001A
001B
*
001D
*
001E
0022
0054
0029
*
0032
0033
0034
0035
002F
*
You can select a trip ON/OFF by parameters.
Problem
External thermal trip
• An external thermal trip is input.
• PTC protection worked.
Emergency stop
• During automatic operation or remote
operation, a stop command is entered
from the operation panel or a remote
input device.
EEPROM fault 1
• A data writing error occurs.
EEPROM fault 2
• Power supply is cut off during
operation and data writing is aborted.
EEPROM fault 3
• A data reading error occurred.
• The control RAM is defective.
Main unit RAM fault
Main unit ROM fault
• The control ROM is defective.
• The control CPU is defective.
CPU fault 1
Communication error
• An error arises during serial
communication.
Current detector fault
• The current detector is defective.
• The error was occurred during Network
Network error
communication.
• The output current decreased to a low-
Low-current
operation
current detection level during operation.
Trip
Undervoltage trip
• The input voltage (in the main circuit) is
(main circuit)
too low.
Ground fault trip
• A ground fault occurs in the output cable
or the motor.
Auto-tuning error
• Check the motor parameter
• The motor with the capacity of 2 classes or less than the inverter is used.
• The output cable is too thin.
• The motor is rotating.
• The inverter is used for loads other than those of three-phase induction motors.
• Circuit board is changed.
Inverter
type error
(Or main circuit/drive circuit board)
• The signal input via VIA is below the
Brea in analog signal
cable
analog sinal detectio level set with
.
• A communications error occurs between
CPU
communications
control CPUs.
error
Excessive torque
• The torque boost parameter
boosted
set too high.
• The motor has too small impedance.
CPU fault 2
• The control CPU is defective.
• The motor shaft is locked.
Step-out
(For PM motor only)
• One output phase is open.
• An impact load is applied.
Possible causes
• Check the external thermal input.
• Check the PTC in the motor.
• Reset the inverter.
• Turn off the inverter, then turn it again. If it
• Turn the power off temporarily and turn it
• Turn off the inverter, then turn it again. If it
• Make a service call.
• Make a service call.
• Make a service call.
• Check the remote control device, cables,
• Make a service call.
• Check the Network device and wiring.
• Enable
• Check the suitable detection level for the
• Make a service call if the setting is
• Check the input voltage.
• Enable
• To cope with a momentary stop due to
• Check the cable and the motor for ground
to
• Make a service call.
• Check the cables for breaks. And check
• Make a service call.
• Re do the Auto-tuning then set
is
• Decrease the setting of the torque boost
• Make a service call.
• Unlock the motor shaft.
• Check the interconnect cables between
M-3
E6581381
Remedies
does not recover from the error, make a
service call.
back on, and then try
operation
again.
does not recover from the error, make a
service call.
etc.
(low-current detection).
system (
,
).
correct.
(undervoltage trip
selection).
undervoltage, enable
(coast stop)
and
(auto-restart).
faults.
.
the setting of input signal or setting value
of
.
parameter
.
the inverter and the motor.
13
.

Advertisement

Table of Contents
loading