6.14 Conducting PID control

: PID control waiting time
: PID control
: Proportional gain
: Integral gain
: Differential gain
• Function
Using feedback signals (4 to 20mA, 0 to 10V) from a detector, process control can be exercised, for
example, to keep the airflow, amount of flow or pressure constant.
[Parameter setting]
Title
PID control waiting time
PID control
Proportional gain
Integral gain
Differential gain
1) External connection
Function
0-2400 [s]
0: Disabled
1: Enabled (Feedback: VIA)
2: Enabled (Feedback: VIB)
0.01-100.0
0.01-100.0
0.00-2.55
F-41
Adjustment range
E6581381
Default setting
0
6
0
0.30
0.20
0.00