Advertisement

5. Basic parameters

Before you operate the inverter, the parameters that you must first program are the basic parameters.
5.1

Setting acceleration/deceleration time

:Automatic acceleration/deceleration
:Acceleration time 1
:Deceleration time 1
• Function
1) For acceleration time 1
0Hz to maximum frequency
2) For deceleration time 1
from maximum frequency
5.1.1
Automatic acceleration/deceleration
This automatically adjusts acceleration and deceleration time in line with load size.
=
* Adjusts the acceleration/deceleration time automatically within the range of 1/8 to 8 times as long as the
time set with the
=
* Automatically adjusts speed during acceleration only. During deceleration, speed is not adjusted
automatically but reduced at the rate set with
Output
frequency (Hz)
Set
programs the time that it takes for the inverter output frequency to go from
.
programs the time that it takes for the inverter output frequency to got
to 0Hz.
or
, depending on the current rating of the inverter.
When load is small
0
Deceleration
Acceleration
time
time
Shorten acceleration/deceleration time
(automatic acceleration/deceleration) to
.
Output
When load is large
frequency (Hz)
0
Time
[sec]
Acceleration
time
Lengthen acceleration/deceleration time
or
.
E-1
E6581381
Time
[sec]
Deceleration
time
5