Section 4
Analog inputs
4.2.2.5
Example on how to connect a wye connected three-phase CT set to the IED
Figure
20
overview of the actions which are needed to make this measurement available to the built-in protection
and control functions within the IED as well.
A
CT 600/5
Star Connected
Protected Object
ANSI13000002 V4 EN-US
Figure 20:
Wye connected three-phase CT set with wye point towards the protected object
62
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs with 1A and 2A
secondary rating
use 5A rated CT input into the IED in order to connect CTs with 5A and 10A
secondary rating
gives an example about the wiring of a wye connected two-phase CT set to the IED. It gives an
For correct terminal designations, see the connection diagrams valid for the delivered
IED.
B
C
I_A
I_B
I_C
I_N
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IED
1
2
3
1MRK 505 370-UUS Rev. K
4
SMAI2
BLOCK
AI3P
REVROT
AI1
5
^GRP2_A
AI2
^GRP2_B
AI3
^GRP2_C
AI4
^GRP2_N
AIN
ANSI13000002-4-en.vsdx
Busbar protection REB670
Application manual
SEMOD55055-352 v12