1MRK 505 370-UUS Rev. K
13.4.1.2
Setting guidelines
Operation: Enabled or Disabled
13.5
Configurable logic blocks
The configurable logic blocks are available in two categories:
Configurable logic blocks that do not propagate the time stamp and the quality of signals. They do
not have the suffix QT at the end of their function block name, for example, SRMEMORY. These
logic blocks are also available as part of an extension logic package with the same number of
instances.
Configurable logic blocks that propagate the time stamp and the quality of signals. They have the
suffix QT at the end of their function block name, for example, SRMEMORYQT.
13.5.1
Application
A set of standard logic blocks, like AND, OR etc, and timers are available for adapting the IED
configuration to the specific application needs. Additional logic blocks that, beside the normal logical
function, have the capability to propagate timestamp and quality are also available. Those blocks have a
designation including the letters QT, like ANDQT, ORQT etc.
13.5.2
Setting guidelines
There are no settings for AND gates, OR gates, inverters or XOR gates as well as, for ANDQT gates,
ORQT gates or XORQT gates.
For normal On/Off delay and pulse timers the time delays and pulse lengths are set from the local HMI or
via the PST tool.
Both timers in the same logic block (the one delayed on pick-up and the one delayed on drop-out) always
have a common setting value.
For controllable gates, settable timers and SR flip-flops with memory, the setting parameters are
accessible via the local HMI or via the PST tool.
13.5.2.1
Configuration
Logic is configured using the ACT configuration tool in PCM600.
Execution of functions as defined by the configurable logic blocks runs according to a fixed sequence
with different cycle times.
For each cycle time, the function block is given an serial execution number. This is shown when using the
ACT configuration tool with the designation of the function block and the cycle time, see example below.
Busbar protection REB670
Application manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 13
Logic
GUID-7E776D39-1A42-4F90-BF50-9B38F494A01E v2
IP11009-1 v4
GUID-F5D6F065-441B-4296-AC56-F4DC1F5487E3 v3
GUID-E6BD982D-9E47-4CC2-9666-6E5CABA414C0 v4
GUID-D93E383C-1655-46A3-A540-657141F77CF0 v4
359