1MRK 505 370-UUS Rev. K
MODEINT (integer)
A start of a new auto reclosing cycle during the set "reset time" is blocked when the set number of
reclosing shots have been reached.
12.2.2.14
External selection of auto reclosing mode
The auto reclosing mode can be selected by use of available logic function blocks. Below is an example
where the choice of mode, ARMode=3ph or ARMode=1/2/3ph, is done from a hardware function key at
the front of the IED, but alternatively there can for example, be a physical selector switch on the front of
the panel which is connected to a binary to integer function block (BTIGAPC).
The connection example for selection of the auto reclosing mode is shown in Figure 133.
INTONE
3
1/3
ANSI09000168 V1 EN-US
Figure 133: Selection of the auto-reclose mode from a hardware functional key in front of the IED
12.2.2.15
Auto reclosing reset timer
The tReset timer defines the time it takes from issue of the breaker closing command, until the auto
recloser resets. Should a new trip occur during this time, it is treated as a continuation of the first fault.
The reclaim timer is started when the circuit breaker closing command is given.
12.2.2.16
Pulsing of the circuit breaker closing command and counter
The circuit breaker closing command, CLOSECB is given as a pulse with a duration set by the tPulse
setting. For circuit breakers without an anti-pumping function, close pulse cutting can be used. It is
selected by the CutPulse setting. In case of a new start pulse (trip), the breaker closing command pulse
is then cut (interrupted). The minimum breaker closing command pulse length is always 50ms. At the
issue of the breaker closing command, the appropriate auto recloser operation counter is incremented.
Busbar protection REB670
Application manual
ARMode
4
1ph + 1*2ph
5
1/2ph + 1*3ph
6
1ph + 1*2/3ph
SLGGIO
PSTO
NAME1
NAME2
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Type of fault
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
SMBRREC (79)
SWPOSN
MODEINT
1st shot
2nd-5th shot
1ph
3ph
2ph
.....
.....
.....
1ph
3ph
2ph
3ph
3ph
.....
1ph
3ph
2ph
.....
3ph
.....
ANSI09000168_1_en.vsd
Section 12
Control
M12391-241 v5
M12391-202 v4
M12391-205 v4
287