Section 14
Monitoring
Setting
k
VGenZeroDb
IGenZeroDb
VBase (set in
Global base)
IBase (set in
Global base)
14.2
Gas medium supervision SSIMG (63)
14.2.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
I
14.2.2
Identification
Function description
Insulation gas monitoring function
14.2.3
Application
Gas medium supervision (SSIMG ,63) is used for monitoring the circuit breaker condition. Proper arc
extinction by the compressed gas in the circuit breaker is very important. When the pressure becomes
too low compared to the required value, the circuit breaker operation shall be blocked to minimize the risk
of internal failure. Binary information based on the gas pressure in the circuit breaker is used as an input
signal to the function. The function generates alarms based on the received information.
384
Short description
Low pass filter coefficient for
power measurement, V and I
Zero point clamping in % of
Vbase
Zero point clamping in % of
Ibase
Base setting for voltage level in
kV
Base setting for current level in
A
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
Binary quality inputs SENPRESQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever there is
no sensor, the quality of the binary input will be low. If sensor quality is low, then lockout and
alarm signals will get reset.
2.2.5
-
IEC 61850
identification
SSIMG
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Selected
Comment
value
0.00
Typically no additional filtering is required
25%
Set minimum voltage level to 25%
3
Set minimum current level to 3%
15,65
Set generator rated phase-to-phase voltage
3690
Set generator rated current
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
63
1MRK 505 370-UUS Rev. K
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v4