1MRK 505 370-UUS Rev. K
OperTimeDelay: Time delay between change of status of trip output and start of main contact separation.
14.5
Event function EVENT
14.5.1
Identification
Function description
Event function
14.5.2
Application
When using a Substation Automation system with LON or SPA communication, time-tagged events can
be sent at change or cyclically from the IED to the station level. These events are created from any
available signal in the IED that is connected to the Event function (EVENT). The EVENT function block is
used for remote communication.
Analog, integer and double indication values are also transferred through the EVENT function.
14.5.3
Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via the local HMI ( Main
Menu /Settings / IED Settings / Monitoring / Event Function ) or via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
The inputs can be set individually as:
•
NoEvents
•
OnSet, at pick-up of the signal
•
OnReset, at drop-out of the signal
•
OnChange, at both pick-up and drop-out of the signal
•
AutoDetect, the EVENT function makes the reporting decision (reporting criteria for integers have no
semantic, prefer to be set by the user)
LONChannelMask or SPAChannelMask
Definition of which part of the event function block that shall generate events:
•
Disabled
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
MinRepIntVal (1 - 16)
A time interval between cyclic events can be set individually for each input channel. This can be set
between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cyclic communication.
Busbar protection REB670
Application manual
IEC 61850
identification
EVENT
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
S00946 V1 EN-US
Section 14
Monitoring
IP14590-1 v2
SEMOD167950-2 v2
M12805-6 v11
IP14841-1 v1
M12811-3 v3
M12811-5 v3
M12811-15 v2
M12811-29 v3
391