ABB Relion 670 Series Applications Manual page 388

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Monitoring
Table 52:
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
VGenZeroDb
IGenZeroDb
VBase (set in
Global base)
IBase (set in
Global base)
SBase (set in
Global base)
Measurement function application for a generator
Single line diagram for this application is given in figure 201.
382
General settings parameters for the Measurement function
Short description
Operation Disabled/Enabled
Magnitude factor to scale power
calculations
Angle compensation for phase
shift between measured I & V
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, V and I
Zero point clamping in % of
Vbase
Zero point clamping in % of
Ibase
Base setting for voltage level in
kV
Base setting for current level in
A
Base setting for power in MVA
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Selected
Comment
value
Enabled
Function must be Enabled
1.000
Typically no scaling is required
180.0
Typically no angle compensation is required. However
here the required direction of P & Q measurement is
towards busbar (Not per IED internal default
direction). Therefore angle compensation have to be
used in order to get measurements in aliment with the
required direction.
L1L2
Only UL1L2 phase-to-phase voltage is available
0.00
Typically no additional filtering is required
25
Set minimum voltage level to 25%
3
Set minimum current level to 3%
35.00
Set LV side rated phase-to-phase voltage
495
Set transformer LV winding rated current
31.5
Set based on rated power
1MRK 505 370-UUS Rev. K
SEMOD54481-110 v8
Busbar protection REB670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reb670

Table of Contents