Figure 147: Application principle for an alternative reservation solution
12.3.8
Interaction between modules
A typical bay with apparatus control function consists of a combination of logical nodes or functions that
are described here:
The Switch controller (SCSWI) initializes all operations for one apparatus. It is the command
interface of the apparatus. It includes the position reporting as well as the control of the position
The Circuit breaker (SXCBR) is the process interface to the circuit breaker for the apparatus control
function.
The Circuit switch (SXSWI) is the process interface to the disconnector or the grounding switch for
the apparatus control function.
The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses, such as operator place
selection and blockings for the complete bay.
The Reservation (QCRSV) deals with the reservation function.
The Protection trip logic (SMPPTRC, 94) connects the "trip" outputs of one or more protection
functions to a common "trip" to be transmitted to SXCBR.
The Autorecloser (SMBRREC, 79) consists of the facilities to automatically close a tripped breaker
with respect to a number of configurable conditions.
The logical node Interlocking (SCILO, 3) provides the information to SCSWI whether it is permitted
to operate due to the switchyard topology. The interlocking conditions are evaluated with separate
logic and connected to SCILO (3).
The Synchronism, energizing check, and synchronizing (SESRSYN, 25) calculates and compares
the voltage phasor difference from both sides of an open breaker with predefined switching
conditions (synchronism check). Also the case that one side is dead (energizing-check) is included.
The Generic Automatic Process Control function, GAPC, handles generic commands from the
operator to the system.
The overview of the interaction between these functions is shown in Figure
Busbar protection REB670
Application manual
IED
IntlReceive
RESGRANT
RES_EXT
IntlReceive
RESGRANT
© 2017 - 2021 Hitachi Power Grids. All rights reserved
SCSWI
SELECTED
SPGAPC
OR
Other SCWI in
IN
the bay
Station bus
IEC05000178-3-en.vsd
Section 12
Control
M16626-3 v11
148
below.