ABB Relion 670 Series Applications Manual page 221

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 370-UUS Rev. K
200MVAr
400kV
IEC09000754 V1 EN-US
Figure 116: Single line diagram for the application example
From figure
1000 200[
=
I
r
IEC09000755 V1 EN-US
or on the secondary CT side:
=
I
r S
_ ec
IEC09000756 V1 EN-US
Note that the SCB rated current on the secondary CT side is important for secondary injection of the
function.
The parameters for the Capacitor bank protection function CBPGAPC are set via the local HMI or
PCM600. The following settings are done for this function:
General Settings:
Operation =Enabled; to enable the function
IBase =289A; Fundamental frequency SCB rated current in primary amperes. This value is used as a
base value for pickup settings of all other features integrated in this function.
Reconnection inhibit feature:
OperationRecIn =Enabled; to enable this feature
Busbar protection REB670
Application manual
400kV
500/1
116
it is possible to calculate the following rated fundamental frequency current for this SCB:
×
MVAr
]
=
289
×
3 400[
kV
]
289
A
=
0.578
A
500 1
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Preprocessing
Function Block
SMAI
A
Capacitor bank
protection function
CBPGAPC
IED
IEC09000754-1-en.vsd
Section 7
Current protection
(Equation 72)
(Equation 73)
215