Section 13
Logic
Name of OUTx
OUT14
OUT15
OUT16
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16) are active equals
65535. This is the highest integer that can be converted by the ITBGAPC function block.
13.12
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
13.12.1
Identification
Function Description
Elapsed time integrator
13.12.2
Application
The function TEIGAPC is used for user-defined logics and it can also be used for different purposes
internally in the IED. An application example is the integration of elapsed time during the measurement of
neutral point voltage or neutral current at earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow indication is fixed to
999999.9 seconds.
13.12.3
Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in seconds. The achievable resolution
of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit float representation
99 999.99 seconds < tAlarm ≤ 999 999.0 seconds
99 999.99 seconds < tWarning ≤ 999 999.0 seconds
The limit for the overflow supervision is fixed at 999999.9 seconds.
368
Type
BOOLEAN
BOOLEAN
BOOLEAN
IEC 61850
identification
TEIGAPC
Note that tAlarm and tWarning are independent settings, that is, there is no check if
tAlarm > tWarning.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Description
Value when activated Value when
Output 14
8192
Output 15
16384
Output 16
32768
IEC 60617
ANSI/IEEE C37.2 device
identification
number
-
-
1MRK 505 370-UUS Rev. K
deactivated
0
0
0
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
Busbar protection REB670
Application manual