ABB Relion 670 Series Applications Manual page 337

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 370-UUS Rev. K
ANSI04000516 V1 EN-US
Figure 162: Switchyard layout A1A2_BS (3)
The signals from other bays connected to the module A1A2_BS are described below.
12.4.5.2
Signals from all feeders
If the busbar is divided by bus-section circuit breakers into bus-sections and both circuit breakers are
closed, the opening of the circuit breaker must be blocked if a bus-coupler connection exists between
busbars on one bus-section side and if on the other bus-section side a busbar transfer is in progress:
(WA1)A1
(WA2)B1
(WA7)C
ABC_LINE
ANSI04000489 V1 EN-US
Figure 163: Busbars divided by bus-section circuit breakers
To derive the signals:
Signal
BBTR_OP
VP_BBTR
EXDU_12
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO), and bus-coupler bay
(ABC_BC) are needed:
Busbar protection REB670
Application manual
WA1 (A1)
189
189G
152
389G
A1A2_BS
Section 1
A1A2_BS
B1B2_BS
ABC_BC
AB_TRAFO
No busbar transfer is in progress concerning this bus-section.
The switch status of BBTR is valid.
No transmission error from any bay connected to busbar 1(A) and 2(B).
© 2017 - 2021 Hitachi Power Grids. All rights reserved
WA2 (A2)
289
289G
489G
en04000516_ansi.vsd
Section 2
ABC_BC
ABC_LINE
AB_TRAFO
en04000489_ansi.vsd
A2
B2
C
Section 12
Control
M15111-4 v3
M15111-6 v4
331