Section 17
Station communication
IEC08000069 V2 EN-US
Figure 218: Example of a station configuration with the IED receiving analog values from both
17.3.2
Faulty merging unit for bay in service
When a merging unit goes faulty while the bay is in service, the protection functions connected to that
merging unit get blocked. In the busbar protection case, the whole busbar protection is then blocked (the
zone to which the bay is connected). This also applies to protection functions in 1 1/2 circuit breaker
applications, where two SV streams from different merging units are combined.
This can be resolved by connecting external binary input signals to the BLOCK input on the respective
SMAI function blocks with the use of ACT. When the BLOCK input on a SMAI function is energized, the
428
Station Wide
SCADA System
Other
Relays
CT
classical measuring transformers and merging units.