Section 11
Secondary system supervision
11.1.3.5
Delta V and delta I
Set the operation mode selector OpDVDI to Enabled if the delta function shall be in operation.
The setting of DVPU should be set high (approximately 60% of VBase) and the current threshold DIPU
low (approximately 10% of IBase) to avoid unwanted operation due to normal switching conditions in the
network. The delta current and delta voltage function shall always be used together with either the
negative or zero sequence algorithm. If VSet
the primary current for operation of dI/dt, the setting of DVPU and DIPU will be given according to
equation
DVPU
=
EQUATION1765-ANSI V2 EN-US
DIPU
=
ANSIEQUATION2385 V2 EN-US
The voltage thresholds VPPU is used to identify low voltage condition in the system. Set VPPU below the
minimum operating voltage that might occur during emergency conditions. A setting of approximately
70% of VBase is recommended.
The current threshold 50P shall be set lower than the IMinOp for the distance protection function. A
5...10% lower value is recommended.
11.1.3.6
Dead line detection
The condition for operation of the dead line detection is set by the parameters IDLDPU for the current
threshold and UDLD< for the voltage threshold.
Set the IDLDPU with a sufficient margin below the minimum expected load current. A safety margin of at
least 15-20% is recommended. The operate value must however exceed the maximum charging current
of an overhead line, when only one phase is disconnected (mutual coupling to the other phases).
Set the VDLDPU with a sufficient margin below the minimum expected operating voltage. A safety
margin of at least 15% is recommended.
11.2
Fuse failure supervision VDSPVC (60)
11.2.1
Identification
Function description
Fuse failure supervision
254
91
and equation 92.
VSet
prim
⋅100
VBase
ISet
prim
⋅100
IBase
© 2017 - 2021 Hitachi Power Grids. All rights reserved
is the primary voltage for operation of dU/dt and ISet
prim
IEC 61850
IEC 60617
identification
identification
VDSPVC
VTS
1MRK 505 370-UUS Rev. K
GUID-02336F26-98C0-419D-8759-45F5F12580DE v7
(Equation 91)
(Equation 92)
GUID-9C5BA1A7-DF2F-49D4-A13A-C6B483DDFCDC v2
GUID-109434B0-23E5-4053-9E6E-418530A07F9C v2
ANSI/IEEE C37.2
device number
60
Busbar protection REB670
Application manual
prim
M13683-78 v4