parameter. Also, being accessible on the single line diagram (SLD), this function block has two control
modes (settable through CtlModel): Dir Norm and SBO Enh.
12.7
Generic communication function for Double Point
indication DPGAPC
12.7.1
Identification
Function description
Generic communication function for
Double Point indication
12.7.2
Application
Generic communication function for Double Point indication (DPGAPC) function block is used to send
double point position indication to other systems, equipment or functions in the substation through IEC
61850-8-1 or other communication protocols. It is especially intended to be used in the interlocking
station-wide logics. To be able to get the signals into other systems, equipment or functions, one must
use other tools, described in the Engineering manual, and define which function block in which systems,
equipment or functions should receive this information.
More specifically, DPGAPC function reports a combined double point position indication output
POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN and CLOSE,
together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the two-bit
integer value of the output POSITION. The timestamp of the output POSITION will have the latest
updated timestamp of the inputs OPEN and CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to intermediated state.
When the value of the input signal VALID changes, the timestamp of the output POSITION will be
updated as the time when DPGAPC function detects the change.
Refer to Table
attributes.
Table 46:
VALID
0
1
1
1
1
352
46
for the description of the input-output relationship in terms of the value and the quality
Description of the input-output relationship
OPEN
-
0
1
0
1
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
DPGAPC
-
CLOSE
-
0
0
1
1
1MRK 505 370-UUS Rev. K
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
ANSI/IEEE C37.2
device number
-
POSITION
Value
Description
0
Intermediate
0
Intermediate
1
Open
2
Closed
3
Bad State
Busbar protection REB670
Application manual
SEMOD55384-1 v4