ABB Relion 670 Series Applications Manual page 349

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 370-UUS Rev. K
corresponding signals from busbar B are used. The same type of module (A1A2_BS) is used for different
busbars, that is, for both bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal
189OPTR
289OPTR
VP189TR
VP289TR
EXDU_BS
For a busbar grounding switch, these conditions from the A1 busbar section are valid:
189OPTR (bay 1/sect.A1)
189OPTR (bay n/sect.A1)
DCOPTR (A1/A2)
VP189TR (bay 1/sect.A1)
VP189TR (bay n/sect.A1)
VPDCTR (A1/A2)
EXDU_BB (bay 1/sect.A1)
EXDU_BB (bay n/sect.A1)
EXDU_DC (A1/A2)
ANSI04000506 V1 EN-US
Figure 180: Signals from any bays in section A1 to a busbar grounding switch in the same section
For a busbar grounding switch, these conditions from the A2 busbar section are valid:
Busbar protection REB670
Application manual
189 is open.
289 is open.
The switch status of 189 is valid.
The switch status of 289 is valid.
No transmission error from the bay BS (bus-section coupler bay) that contains the
above information.
. . .
AND
. . .
. . .
. . .
AND
. . .
. . .
. . .
AND
. . .
. . .
© 2017 - 2021 Hitachi Power Grids. All rights reserved
BB_DC_OP
VP_BB_DC
EXDU_BB
en04000506_ansi.vsd
Section 12
Control
343