SMAI function delivers a magnitude of zero with good quality for all the channels. Thus, this has no effect
on a busbar protection, nor protections in an 1 1/2 circuit breaker configuration.
GUID-F723C815-3A26-481A-B046-21D1243E7080 V1 EN-US
Figure 219: Configuration of current inputs using SMAIs in a 1 1/2 circuit breaker application.
Busbar protection REB670
Application manual
SMAI function blocks exist in different cycle times, and all the SMAI blocks that receive
SV streams from the merging units must have the block input signal configured in the
same way to get the correct behavior.