configurations must abide by the following rules: Normally apparatus position is connected with contacts
showing both open (b-type) and closed positions (a-type).
WA1_QA1:
BUS1_OP/CL = Position of TIE_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of WA2_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = 1 1/2 bus CB
TIE_QA1:
BUS1_OP/CL = Position of WA1_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of WA2_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = Tie CB
WA2_QA1:
BUS1_OP/CL = Position of WA1_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of TIE_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = 1 1/2 bus alt. CB
If only two SESRSYN functions are provided in the same IED, the connections and settings are
according to the SESRSYN functions for WA1_QA1 and TIE_QA1.
12.1.4
Setting guidelines
The setting parameters for the Synchronizing, synchronism check and energizing check function
SESRSYN (25) are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN (25) function via the LHMI.
Common base IED value for primary voltage ( VBase ) is set in a Global base value function, GBASVAL,
found under Main menu/ /Configuration/Power system /GlobalBaseValue/GBASVAL_X /VBase. The
SESRSYN (25) function has one setting for the bus reference voltage (GblBaseSelBus) and one setting
for the line reference voltage (GblBaseSelLine) which independently of each other can be set to select
one of the twelve GBASVAL functions used for reference of base values. This means that the reference
voltage of bus and line can be set to different values. The settings for the SESRSYN (25) function are
Busbar protection REB670
Application manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 12
Control
M12550-3 v15
275