Section 20
Basic IED functions
ProductDef
FirmwareVer
ProductVer
IEDMainFunType
SerialNo
OrderingNo
ProductionDate
20.3
Measured value expander block RANGE_XP
20.3.1
Identification
Function description
Measured value expander block
20.3.2
Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU), current
and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic
communication I/O functions (MVGAPC) are provided with measurement supervision functionality. All
measured values can be supervised with four settable limits, that is low-low limit, low limit, high limit and
high-high limit. The measure value expander block ( RANGE_XP) has been introduced to be able to
translate the integer output signal from the measuring functions to 5 binary signals, that is below low-low
limit, below low limit, normal, above high-high limit or above high limit. The output signals can be used as
conditions in the configurable logic.
464
Describes the type of the IED. Example: REL670
Describes the release number from the production. Example: 2.1.0
Describes the firmware version.
The firmware version can be checked from Main menu/Diagnostics/IED status/Product
identifiers
Firmware version numbers run independently from the release production numbers. For every
release number there can be one or more firmware versions depending on the small issues
corrected in between releases.
Describes the product version. Example: 2.1.0
1 is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new hardware added to the
product
3 is the Major revision of the manufactured product this means, functions or hardware is either changed or
enhanced in the product
Main function type code according to IEC 60870-5-103. Example: 128 (meaning line
protection).
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
1MRK 505 370-UUS Rev. K
ANSI/IEEE C37.2
device number
-
Busbar protection REB670
Application manual
SEMOD52451-1 v2
SEMOD113212-2 v3
SEMOD52434-4 v6