1MRK 505 370-UUS Rev. K
100 MVA
100 MVA
15.65kV
ANSI09000041 V1 EN-US
Figure 201: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 201, it is necessary to do the
following:
1.
Set correctly all CT and VT data and phase angle reference channel PhaseAngleRef using PCM600
for analog input channels
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following table:
Table 53:
Setting
Operation
PowAmpFact
PowAngComp
Mode
Table continues on next page
Busbar protection REB670
Application manual
230kV Busbar
300/5
15/0.12kV
V
V
,
AB ,
P
Q
G
4000/5
General settings parameters for the Measurement function
Short description
Operation Off/On
Amplitude factor to scale power
calculations
Angle compensation for phase
shift between measured I & V
Selection of measured current
and voltage
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IED
BC
ANSI09000041-1-en.vsd
Selected
Comment
value
On
Function must be On
1.000
Typically no scaling is required
0.0
Typically no angle compensation is required. As well
here required direction of P & Q measurement is
towards protected object (as per IED internal default
direction)
Arone
Generator VTs are connected between phases (V-
connected)
Section 14
Monitoring
383