1MRK 505 370-UUS Rev. K
12.1.3.3
Single circuit breaker with double busbar, internal voltage selection
V REF 1
V REF 2
VA/VB/VC
ANSI10000095 V1 EN-US
Figure 129: Connection of the SESRSYN function block in a single breaker, double busbar
When internal voltage selection is needed, the voltage transformer circuit connections are made
according to figure 129. The voltage from the busbar 1 VT is connected to V3PB1 and the voltage from
busbar 2 is connected to V3PB2. The voltage from the line VT is connected to V3PL1. The positions of
the disconnectors and VT fuses shall be connected as shown in figure 129. The voltage selection
parameter CBConfig is set to Double bus.
Busbar protection REB670
Application manual
Bus 1
Bus 2
Fuse
bus1 Voltage
VT
Fuse
bus2 Voltage
VT
189
152
lineVoltage /1/2/3
Fuse
VT
Line
arrangement with internal voltage selection
© 2017 - 2021 Hitachi Power Grids. All rights reserved
289
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI10000095-1-en.vsd
Section 12
Control
M12326-3 v7
271