Note that the IEC/UCA 61850-9-2LE standard does not specify the quality of the sampled values, only
the transportation. Thus, the accuracy of the current and voltage inputs to the merging unit and the
inaccuracy added by the merging unit must be coordinated with the requirement for actual type of
protection function.
Factors influencing the accuracy of the sampled values from the merging unit are for example anti
aliasing filters, frequency range, step response, truncating, A/D conversion inaccuracy, time tagging
accuracy etc.
In principle the accuracy of the current and voltage transformers, together with the merging unit, shall
have the same quality as direct input of currents and voltages.
Busbar protection REB670