ABB Relion 670 Series Applications Manual page 211

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 370-UUS Rev. K
IEC06000556 V1 EN-US
Figure 111: For low forward power the set angle should be 0° in the underpower function
TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.
Hysteresis1(2) is given in p.u. of generator rated power according to equation 57.
=
S
N
EQUATION2047 V1 EN-US
The drop out power will be Power1(2) + Hysteresis1(2).
The possibility to have low pass filtering of the measured power can be made as shown in the formula:
S TD S
=
EQUATION1893-ANSI V1 EN-US
Where
S
S
old
S
Calculated
TD
The value of k=0.92 is recommended in generator applications as the trip delay is normally quite long.
The calibration factors for current and voltage measurement errors are set % of rated current/voltage:
IMagComp5, IMagComp30, IMagComp100
Busbar protection REB670
Application manual
Q
Operate
Angle1(2) = 0
Power1(2)
×
×
3 VBase IBase
(
)
TD S
+
1
Old
Calculated
is a new measured value to be used for the protection function
is the measured value given from the function in previous execution cycle
is the new calculated value in the present execution cycle
is settable parameter
© 2017 - 2021 Hitachi Power Grids. All rights reserved
°
P
en06000556.vsd
Section 7
Current protection
(Equation 57)
(Equation 58)