Section 14
Monitoring
Function description
Current sequence component
measurement
Voltage sequence component
measurement
Phase-neutral voltage measurement
14.1.4
Application
Measurement functions are used for power system measurement, supervision and reporting to the local
HMI, monitoring tool within PCM600 or to station level for example, via IEC 61850. The possibility to
continuously monitor measured values of active power, reactive power, currents, voltages, frequency,
power factor etc. is vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the power system.
Additionally, it can be used during testing and commissioning of protection and control IEDs in order to
verify proper operation and connection of instrument transformers (CTs and VTs). During normal service
by periodic comparison of the measured value from the IED with other independent meters the proper
operation of the IED analog measurement chain can be verified. Finally, it can be used to verify proper
direction orientation for distance or directional overcurrent protection function.
All measured values can be supervised with four settable limits that is, low-low limit, low limit, high limit
and high-high limit. A zero clamping reduction is also supported, that is, the measured value below a
settable limit is forced to zero which reduces the impact of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level when change in
measured value is above set threshold limit or time integral of all changes since the last time value
updating exceeds the threshold limit. Measure value can also be based on periodic reporting.
Main menu /Measurement /Monitoring /Service values /CVMMXN
The measurement function, CVMMXN, provides the following power system quantities:
P, Q and S: three phase active, reactive and apparent power
PF: power factor
V: phase-to-phase voltage magnitude
I: phase current magnitude
F: power system frequency
,
The measuring functions CMMXU, VMMXU and VNMMXU provide physical quantities:
374
IEC 61850
identification
CMSQI
VMSQI
VNMMXU
The available measured values from an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
I1, I2, I0
SYMBOL-VV V1 EN-US
-
U1, U2, U0
SYMBOL-TT V1 EN-US
-
U
SYMBOL-UU V1 EN-US
1MRK 505 370-UUS Rev. K
SEMOD54488-4 v12
Busbar protection REB670
Application manual