1MRK 505 370-UUS Rev. K
No.
StartMode
16
FollowStart&M
ode
17
FollowStart&M
ode
18
FollowStart&M
ode
No.
StartMode
FunctionMode = Current or CB Pos
19
LatchedStart
20
LatchedStart
21
LatchedStart
Table continues on next page
Busbar protection REB670
Application manual
RetripMode
t1 and t2 initiated
with
Off
external START
and CBCLD
input has logical
value one
UseFunctionMode
external START
and CBCLD
input has logical
value one
Always
external START
and CBCLD
input has logical
value one
RetripMode
t1 and t2 initiated
with
Off
external START
UseFunctionMode
external START
Always
external START
© 2017 - 2021 Hitachi Power Grids. All rights reserved
When t1 has
When t2 has elapsed,
elapsed, TRRET
TRBU will be given if
will
never be given
be given if CBCLD
input has logical
value one and
external START is
present
be given if CBCLD
be given if CBCLD
input has logical
input has logical
value one and
value one and
external START is
external START is
present
present
be given if external
be given if CBCLD
START is present
input has logical
value one and
external START is
present
When t1 has
When t2 has elapsed,
elapsed, TRRET
TRBU will be given if
will
never be given
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
be given if current
current is above set
is above set level
level of IPh> and
of IPh> and higher
higher than
than I>BlkCBPos
I>BlkCBPos or
or CBCLD input
CBCLD input has
has logical value
logical value one
one when current
when current is
is smaller than
smaller than
I>BlkCBPos
I>BlkCBPos
always be given
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
Section 7
Current protection
t1 and t2 will be
stopped (reset) if
CBCLD input has
logical value zero or
external START
disappears
CBCLD input has
logical value zero or
external START
disappears
CBCLD input has
logical value zero or
external START
disappears
t1 and t2 will be
stopped (reset) if
t1 and (t2 or t2MPh)
and 150ms expires
and current is below
set level of IPh> or
CBCLD input has
logical value zero
t1 and (t2 or t2MPh)
and 150ms expires
and current is below
set level of IPh> or
CBCLD input has
logical value zero
t1 and (t2 or t2MPh)
and 150ms expires
and current is below
set level of IPh> or
CBCLD input has
logical value zero
199