Section 7
Current protection
7.9.3
Setting guidelines
GlobalBaseSel: Selects the global base value group used by the function to define IBase, VBase and
SBase. Note that this function will only use IBase value.
Operation: With the parameter Operation the function can be set Enabled/Disabled.
Mode: The voltage and current used for the power measurement. The setting possibilities are shown in
table 37.
Table 37:
Set value Mode
A,B,C
Arone
PosSeq
A,B
B,C
C,A
A
B
C
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting Angle1(2) is larger
than the set pick up power value Power1(2)
208
Complex power calculation
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Formula used for complex power calculation
*
*
=
×
+
×
S
V
I
V
I
A
A
B
B
EQUATION2038 V1 EN-US
*
-
=
×
×
S
V
I
V
AB
A
BC
EQUATION2039 V1 EN-US
*
= ×
×
S
3 V
I
PosSeq
PosSeq
EQUATION2040 V1 EN-US
*
*
-
=
×
)
S
V
(I
I
AB
A
B
EQUATION2041 V1 EN-US
*
*
-
=
×
)
S
V
(I
I
B
C
BC
EQUATION2042 V1 EN-US
*
*
-
=
×
)
S
V
(I
I
C
A
CA
EQUATION2043 V1 EN-US
*
= ×
×
S 3 V
I
A
A
EQUATION2044 V1 EN-US
*
= ×
×
S
3 V
I
B
B
EQUATION2045 V1 EN-US
*
= ×
×
S
3 V
I
C
C
EQUATION2046 V1 EN-US
1MRK 505 370-UUS Rev. K
*
+
×
V
I
C
C
(Equation 60)
*
I
C
(Equation 61)
(Equation 62)
(Equation 63)
(Equation 64)
(Equation 65)
(Equation 66)
(Equation 67)
(Equation 68)
Busbar protection REB670
Application manual
SEMOD172150-4 v7