ABB Relion 670 Series Applications Manual page 369

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 370-UUS Rev. K
Name of input
IN14
IN15
IN16
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16) are active that
is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the B16I
function block.
13.8
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC
13.8.1
Identification
Function description
Boolean to integer conversion with
logical node representation, 16 bit
13.8.2
Application
Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is used to transform a
set of 16 binary (logical) signals into an integer. BTIGAPC has a logical node mapping in IEC 61850.
The BTIGAPC function will transfer a combination of up to 16 binary inputs INx where 1≤x≤16 to an
integer. Each INx represents a value according to the table below from 0 to 32768. This follows the
general formula: INx = 2
on the output OUT as a sum of the values of all the inputs INx that are activated. OUT is an integer.
When all INx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer 65535 is
available on the output OUT. BTIGAPC function is designed for receiving up to 16 booleans input locally.
If the BLOCK input is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block BTIGAPC.
Name of input
IN1
IN2
IN3
IN4
IN5
Table continues on next page
Busbar protection REB670
Application manual
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
IEC 61850
identification
BTIGAPC
x-1
where 1≤x≤16. The sum of all the values on the activated INx will be available
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Description
Value when
activated
Input 14
8192
Input 15
16384
Input 16
32768
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
Input 5
16
Section 13
Logic
Value when
deactivated
0
0
0
SEMOD175753-1 v4
SEMOD175757-2 v5
SEMOD175849-4 v6
Value when
deactivated
0
0
0
0
0
363

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reb670

Table of Contents