ABB Relion 670 Series Applications Manual page 274

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 12
Control
HMI, through selector switch function block, but alternatively there can for example, be a physical
selector switch on the front of the panel which is connected to a binary to integer function block (B16I).
If the PSTO input is used, connected to the Local-Remote switch on the local HMI, the choice can also
be from the station HMI system, typically Hitachi Power grids Microscada through IEC 61850–8–1
communication.
The connection example for selection of the manual energizing mode is shown in figure 126. Selected
names are just examples but note that the symbol on the local HMI can only show the active position of
the virtual selector.
INTONE
OFF
DL
DB
DLB
ANSI09000171 V1 EN-US
Figure 126: Selection of the energizing direction from a local HMI symbol through a selector switch
12.1.3
Application examples
The synchronism check function block can also be used in some switchyard arrangements, but with
different parameter settings. Below are some examples of how different arrangements are connected to
the IED analog inputs and to the function block SESRSYN, 25. One function block is used per circuit
breaker.
268
SLGGIO
PSTO
NAME1
SWPOSN
NAME2
NAME3
NAME4
function block.
The input used below in example are typical and can be changed by use of configuration
and signal matrix tools.
The SESRSYN and connected SMAI function block instances must have the same cycle
time in the application configuration.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
SESRSYN (25)
MENMODE
ANSI09000171_1_en.vsd
1MRK 505 370-UUS Rev. K
M12323-3 v7
Busbar protection REB670
Application manual