ABB Relion 670 Series Applications Manual page 387

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 370-UUS Rev. K
Setting
IAngComp5
IAngComp30
IAngComp100
Measurement function application for a power transformer
Single line diagram for this application is given in figure 200.
31.5 MVA
ANSI09000040 V1 EN-US
Figure 200: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 200, it is necessary to do the
following:
1.
Set correctly all CT and VT and phase angle reference channel PhaseAngleRef data using PCM600
for analog input channels
2.
Connect, in PCM600, measurement function to LV side CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following table 52:
Busbar protection REB670
Application manual
Short Description
Angle calibration for current at
5% of In
Angle pre-calibration for current
at 30% of In
Angle pre-calibration for current
at 100% of In
132kV Busbar
200/5
P
Q
500/5
33kV Busbar
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Selected
Comments
value
0.00
0.00
0.00
IED
V
AB
33kV 120V
/
3
3
ANSI09000040-1-en.vsd
Section 14
Monitoring
SEMOD54481-61 v9
381