Section 11
Secondary system supervision
DelI>: This setting is used to detect the pickup value for instantaneous sample, RMS, DFT mag based
delta detection. Set a typical value of 200% of IBase to use this function as fault detection.
DeltaT: This setting defines the number of old cycles data to be used for delta calculation in RMS/DFT
Mag mode. Typical value is 2 cycles.
tHold: This setting defines the pulse length for supervision pickup signal. Typical value is 100 ms.
EnaHarm2Blk: This setting should be set to ON, to enable blocking for heavy inrush currents or other
sources of 2
Harm2BlkLev: This is the blocking level of 2
setting is 15% of fundamental signal.
EnStValAdap: This setting should be set to ENABLE in special networks where settings in the network
are adapted with respect to 3
Harm3Level: This is the set level of 3
should be modified. Typical setting is 15% of fundamental signal.
StValGrad: This setting is used to modify the DelI> based on 3
modify the DelI>.
11.5
Delta supervision of real input DELSPVC
11.5.1
Identification
Function description
Delta supervision of real input
11.5.2
Application
Delta supervision of real input DELSPVC is a general processed input delta supervision. It is used to
configure any processed inputs such as:
Power (S)
Active power (P)
Reactive power (P)
Thermal heat content (ɸ)
Energy
The change over time of these quantities with respect to the old value can be supervised with this
function.
11.5.3
Setting guidelines
Operation: This setting is used to enable/disable the delta supervision function.
MinStVal: The minimum start level of the function. If the input is below this level, the function will be
blocked. It should be set depending on the input connected.
260
nd
harmonic injections.
rd
harmonic level.
rd
IEC 61850
identification
DELSPVC
© 2017 - 2021 Hitachi Power Grids. All rights reserved
nd
harmonic with respect to the fundamental signal. Typical
harmonic with respect to fundamental signal at which the DelI>
rd
harmonic level. Typical setting is 10% to
IEC 60617
identification
1MRK 505 370-UUS Rev. K
GUID-470F7470-F3D1-46BC-B0EA-CD180FBA0AB2 v1
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1
ANSI/IEEE C37.2
device number
GUID-C7F56ACE-D1F2-4F33-96CA-108D7F11FDD5 v1
GUID-0D420893-4266-4EED-8790-1FFA0F41C962 v1
Busbar protection REB670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reb670

Table of Contents