1MRK 505 370-UUS Rev. K
DelSt>: This setting is used to set the start value for delta detection.
DeltaT: This setting defines the number of execution cycles of old data to be used for delta calculation.
That is, if DeltaT setting is set as 6 for a 3 ms function, an 18 ms old value will be used to compare the
change against.
tHold: This setting defines the pulse length for the start signal. A typical value of this setting is 100 ms.
Busbar protection REB670
Application manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 11
Secondary system supervision
261