ABB Relion 670 Series Applications Manual page 292

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 12
Control
12.2.2.10
ARMode = 1/2ph, 1-phase or 2-phase reclosing in the first shot
At single-pole or two-pole tripping, the operation is as in the example described above, program mode
1/2/3ph. If the first reclosing shot fails, a three-pole trip will be issued and three-pole auto reclosing can
follow, if selected. In the event of a three-pole trip, TR3P input high, the auto recloser will be inhibited and
no auto reclosing takes place.
12.2.2.11
ARMode = 1ph+1*2ph, 1-phase or 2-phase reclosing in the first shot
At single-pole tripping, the operation is as in the above described example, program mode 1/2/3ph. The
single-pole auto reclosing attempt can be followed by three-pole reclosing, if selected. At two-pole trip, a
failure of a two-pole auto reclosing attempt will inhibit the auto recloser. No more shots are attempted. If
the first trip is a three-pole trip, the auto-reclosing will be inhibited. No more shots are attempted. The
expression "1*2ph" should be understood as "Only one shot at two-phase auto reclosing".
12.2.2.12
ARMode = 1/2ph + 1*3ph, 1-phase, 2-phase or 3-phase reclosing in the first
shot
At single-pole or two-pole tripping, the operation is as in the example described above, program mode
1/2/3ph. If the first reclosing shot fails, a three-pole trip will be issued and three-pole reclosing will follow,
if selected. At three-pole trip, a failure of a three-pole auto reclosing attempt will inhibit the auto recloser.
No more shots are attempted. The expression "1*3ph" should be understood as "Only one shot at three-
pole auto reclosing".
12.2.2.13
ARMode = 1ph + 1*2/3ph, 1-phase, 2-phase or 3-phase reclosing in the first
shot
At single-pole or two-pole tripping, the operation is as in the above described example, program mode
1/2/3ph. If the first reclosing shot fails, a three-pole trip will be issued and three-pole reclosing will follow,
if selected. At two-pole or three-pole trip a failure of a two-pole or three-pole auto reclosing attempt will
inhibit the auto recloser. No more shots are attempted. The expression "1*2/3ph" should be understood
as "Only one shot at two-pole or three-pole auto reclosing".
Table 41:
MODEINT (integer)
Table continues on next page
286
Type of reclosing shots at different settings of ARMode or integer inputs to MODEINT
ARMode
1
3ph
2
1/2/3ph
3
1/2ph
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Type of fault
1st shot
1ph
3ph
2ph
3ph
3ph
3ph
1ph
1ph
2ph
2ph
3ph
3ph
1ph
1ph
2ph
2ph
3ph
.....
1MRK 505 370-UUS Rev. K
M12391-136 v5
M12391-139 v5
GUID-9C2FB801-F324-465E-8FD2-715A9C3D0BD8 v2
M12391-146 v5
2nd-5th shot
3ph
3ph
3ph
3ph
3ph
3ph
3ph
3ph
.....
Busbar protection REB670
Application manual