Section 12
Control
ON
OFF
BLKON
BLKOFF
RESET
PLCLOST
RI
SKIPHS
THOLHOLD
TRSOTF
CBREADY
52a
RSTCOUNT
WAIT
*) Other input/output signals as in previous single
breaker arrangements
ANSI04000137 V3 EN-US
Figure 138: Additional input and output signals at multi-breaker arrangement. The connections can
12.2.3.2
Auto recloser settings
The settings for the auto recloser are set using the local HMI (LHMI) or PCM600.
This setting guideline describes the settings of the auto recloser using the LHMI.
296
The signals can be cross-connected to allow simple changing of the priority by just
setting the High and the Low priorities without changing the configuration. The input 52a
for each circuit breaker is important in multi-breaker arrangements to ensure that the
circuit breaker was closed at the beginning of the cycle. If the High priority circuit breaker
is not closed the High priority moves to the low priority circuit breaker.
Terminal '' Master "
Priority = High
SMBRREC (79)
BLOCKED
SETON
INPROGR
ACTIVE
INHIBIT
UNSUCCL
SUCCL
READY
CB1
CLOSEMD
RI_HS
PERMIT1P
PREP3P
1PT1
2PT1
3PT1
3PT2
3PT3
SYNC
3PT4
WAIT
3PT5
WFMASTER
Terminal '' Slave "
Priority = Low
SMBRREC (79)
ON
BLOCKED
OFF
SETON
BLKON
INPROGR
BLOCKOFF
ACTIVE
INHIBIT
UNSUCCL
RESET
SUCCL
PLCLOST
READY
RI
CB2
CLOSEMD
RI_HS
PERMIT1P
SKIPHS
PREP3P
TRSOTF
1PT1
THOLHOLD
2PT1
CBREADY
3PT1
52a
3PT2
SYNC
3PT3
3PT4
3PT5
WFMASTER
ANSI04000137-3-en.vsd
be made "symmetrical" to make it possible to control the priority by the settings,
Priority: High/Low
© 2017 - 2021 Hitachi Power Grids. All rights reserved
x
x
1MRK 505 370-UUS Rev. K
GUID-74980A07-CF89-488F-AB17-E5351D0032EE v1
Busbar protection REB670
Application manual