ABB Relion 670 Series Applications Manual page 466

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 19
Security
The information can, in addition to be viewed on the built in HMI, also be retrieved with the aid of a PC
with PCM600 installed and by using the Event Monitoring Tool. The PC can either be connected to the
front port, or to the port at the back of the IED.
19.3
Change lock CHNGLCK
19.3.1
Application
Change lock function CHNGLCK is used to block further changes to the IED configuration once the
commissioning is complete. The purpose is to make it impossible to perform inadvertent IED
configuration and setting changes.
However, when activated, CHNGLCK will still allow the following actions that does not involve
reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group
The binary input controlling the function is defined in ACT or SMT. The CHNGLCK function is configured
using ACT.
LOCK
Change lock functionality can be temporarily disabled/overridden using Maintenance menu.
Maintenance menu/Recovery Menu (Password Protected)/Turn off Change-lock (Temporary).
Turning off the change-lock will override the change lock function until the next reboot of the IED. In this
case, the change lock function cannot be activated, and the Override output will indicate that the change-
lock is overridden.
460
Binary input signal that will activate/deactivate the function, defined in ACT or SMT.
When CHNGLCK has a logical one on its input, then all attempts to modify the IED
configuration and setting will be denied and the message "Error: Changes blocked" will
be displayed on the local HMI; in PCM600 the message will be "Operation denied by
active ChangeLock". The CHNGLCK function should be configured so that it is controlled
by a signal from a binary input card. This guarantees that by setting that signal to a
logical zero, CHNGLCK is deactivated. If any logic is included in the signal path to the
CHNGLCK input, that logic must be designed so that it cannot permanently issue a
logical one to the CHNGLCK input. If such a situation would occur in spite of these
precautions, then please contact the local Hitachi Power grids representative for
remedial action.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 370-UUS Rev. K
GUID-B48775D0-ACF0-49C6-A7F6-69AF37F1C68F v1
GUID-51EEC9C7-8ECF-4546-BC26-326861654340 v4
GUID-8C333BC0-AA7A-4ED1-A772-18C22E8EEE62 v7
Busbar protection REB670