1MRK 505 370-UUS Rev. K
Example for use of GRP_OFF signal in FXDSIGN
The Restricted earth fault function (REFPDIF) (87N) can be used both for auto-transformers and normal
transformers.
When used for auto-transformers, information from both windings parts, together with the neutral point
current, needs to be available to the function. This means that three inputs are needed.
ANSI11000083 V1 EN-US
Figure 195: REFPDIF (87N) function inputs for autotransformer application
For normal transformers only one winding and the neutral point is available. This means that only two
inputs are used. Since all group connections are mandatory to be connected, the third input needs to be
connected to something, which is the GRP_OFF signal in FXDSIGN function block.
FXDSIGN
GRP_OFF
ANSI11000084 V1 EN-US
Figure 196: REFPDIF (87N) function inputs for normal transformer application
Busbar protection REB670
Application manual
REFPDIF (87N)
I3PW1CT1
I3PW2CT1
I3P
ANSI11000083_1_en.vsd
REFPDIF (87N)
I3PW1CT1
I3PW2CT1
I3P
ANSI11000084_1_en.vsd