1MRK 505 370-UUS Rev. K
Examples of adaptive frequency tracking
Busbar protection REB670
Application manual
Even if the user sets the AnalogInputType of a SMAI block to "Current", the
MinValFreqMeas is still visible. However, using the current channel values as base for
frequency measurement is not recommendable for a number of reasons, not last
among them being the low level of currents that one can have in normal operating
conditions.
Preprocessing block shall only be used to feed functions within the same execution
cycles (e.g. use preprocessing block with cycle 1 to feed transformer differential
protection). The only exceptions are measurement functions (CVMMXN,
CMMXU,VMMXU, etc.) which shall be fed by preprocessing blocks with cycle 8.
When two or more preprocessing blocks are used to feed one protection function (e.g.
over-power function GOPPDOP), it is of outmost importance that parameter setting
DFTReference has the same set value for all of the preprocessing blocks involved
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 20
Basic IED functions
471