14.2.4
Setting guidelines
The parameters for Gas medium supervision SSIMG can be set via local HMI or Protection and Control
Manager PCM600.
Operation: This is used to disable/enable the operation of gas medium supervision, that is, Off/On.
PresAlmLimit: This is used to set the limit for a pressure alarm condition in the circuit breaker.
PresLOLimit: This is used to set the limit for a pressure lockout condition in the circuit breaker.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in the circuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in the circuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication, given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication, given in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication, given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout indication, given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set time delay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set time delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a set time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set time delay in s.
14.3
Liquid medium supervision SSIML (71)
14.3.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
I
Busbar protection REB670
Application manual
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
Binary quality inputs SENLVLQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever there is
no sensor, the quality of the binary input will be low. If sensor quality is low, then lockout and
alarm signals will get reset.
2.2.5
-
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 14
Monitoring
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v4
GUID-37669E94-4830-4C96-8A67-09600F847F23 v4
GUID-751C8C78-891D-423B-825A-0774D0B6C658 v2
385