Section 7
Current protection
HarmBlkSOTF: This is used to On/Off harmonic restrain during SOTF conditions.
tSOTF: Time delay for operation of the SOTF function. The setting range is 0.000 - 60.000 s in step of
0.001 s. The default setting is 0.100 s.
t4U: Time interval when the SOTF function is active after breaker closing. The setting range is 0.000 -
60.000 s in step of 0.001 s. The default setting is 1.000 s.
ActUndrTimeSel: Describes the mode to activate the sensitive undertime function. The function can be
activated by Circuit breaker position (change) or Circuit breaker command.
tUnderTime: Time delay for operation of the sensitive undertime function. The setting range is 0.000 -
60.000 s in step of 0.001 s. The default setting is 0.300 s.
7.3.3.5
Settings for each step (x = 1, 2, 3 and 4)
Operation: Sets the protection to Enabled or Disabled.
DirModeSelx: The directional mode of step x. Possible settings are Disabled/Non-directional/Forward/
Reverse.
Characteristx: Selection of time characteristic for step x. Definite time delay and different types of inverse
time characteristics are available.
Inverse time characteristic enables fast fault clearance of high current faults at the same time as
selectivity to other inverse time phase overcurrent protections can be assured. This is mainly used in
radial fed networks but can also be used in meshed networks. In meshed networks, the settings must be
based on network fault calculations.
To assure selectivity between different protections, in the radial network, there has to be a minimum time
difference Dt between the time delays of two protections. To determine the shortest possible time
difference, the operation time of protections, breaker opening time and protection resetting time must be
known. These time delays can vary significantly between different protective equipment. The following
time delays can be estimated:
Protection trip time:
Protection resetting time:
Breaker opening time:
The different characteristics are described in the technical reference manual.
tx: Definite time delay for step x. The definite time tx is added to the inverse time when inverse time
characteristic is selected. Note that the value set is the time between activation of the start and the trip
outputs.
Pickup"x": Operate residual current level for step x given in % of IB.
INx>Max and INx>Min should only be changed if remote setting of operation current level, INx>, is used.
The limits are used for decreasing the used range of the INx> setting. If INx> is set outside INx>Max and
INx>Min, the closest of the limits to INx> is used by the function. If INx>Max is smaller than INx>Min, the
limits are swapped.
kx: Time multiplier for the dependent (inverse) characteristic for step x.
170
15-60 ms
15-60 ms
20-120 ms
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 370-UUS Rev. K
M15282-9 v13