ABB Relion 670 Series Applications Manual page 212

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
VMagComp5, VMagComp30, VMagComp100
IMagComp5, IMagComp30, IMagComp100
The angle compensation is given as difference between current and voltage angle errors.
The values are given for operating points 5, 30 and 100% of rated current/voltage. The values should be
available from instrument transformer test protocols.
7.9
Directional overpower protection GOPPDOP (32)
7.9.1
Identification
Function description
Directional overpower protection
7.9.2
Application
The task of a generator in a power plant is to convert mechanical energy available as a torque on a
rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it does not cover
bearing losses and ventilation losses. Then, the synchronous generator becomes a synchronous motor
and starts to take electric power from the rest of the power system. This operating state, where individual
synchronous machines operate as motors, implies no risk for the machine itself. If the generator under
consideration is very large and if it consumes lots of electric power, it may be desirable to disconnect it to
ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state. The task of the
reverse power protection is to protect the turbine and not to protect the generator itself.
Steam turbines easily become overheated if the steam flow becomes too low or if the steam ceases to
flow through the turbine. Therefore, turbo-generators should have reverse power protection. There are
several contingencies that may cause reverse power: break of a main steam pipe, damage to one or
more blades in the steam turbine or inadvertent closing of the main stop valves. In the last case, it is
highly desirable to have a reliable reverse power protection. It may prevent damage to an otherwise
undamaged plant.
During the routine shutdown of many thermal power units, the reverse power protection gives the tripping
impulse to the generator breaker (the unit breaker). By doing so, one prevents the disconnection of the
unit before the mechanical power has become zero. Earlier disconnection would cause an acceleration of
the turbine generator at all routine shutdowns. This should have caused overspeed and high centrifugal
stresses.
When the steam ceases to flow through a turbine, the cooling of the turbine blades will disappear. Now, it
is not possible to remove all heat generated by the windage losses. Instead, the heat will increase the
temperature in the steam turbine and especially of the blades. When a steam turbine rotates without
206
IEC 61850
identification
GOPPDOP
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
32
P >
2
DOCUMENT172362-IMG158942
V2 EN-US
1MRK 505 370-UUS Rev. K
SEMOD172360-1 v4
SEMOD176574-2 v4
SEMOD172358-4 v2
Busbar protection REB670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reb670

Table of Contents